P a r a m e t e r
P a r a m e t e r
8 Parameter
The KACO XP100-HV parameters are pre-confi gured for operation. These parameters make KACO XP series invert-
ers to be powerful, effi
cient and perfectly suited for implementing large-scale PV plants.
The KACO XP100-HV parameters are subdivided into ten:
•
PV
Array
Setting values for MPPT control and startup of inverter
•
Inverter
Setting values for inverter rate and cabinet temperature
•
Grid
Setting values for abnormal and rated levels of grid
•
Time
Setting values for the current time
•
Digital
Setting values for digital interface
•
Analog
Setting values for analog interface
•
Controller
Setting values for inverter control
•
Trace
Setting values for inverter fault analysis
•
Off set
Setting values for sensing off set calibration
•
Gain
Setting values for sensing gain calibration
8.1
PV Array Parameters
Parameters
Units
Ranges
Descriptions
Default
MPPT Enable
N/A
On(1), Off (0)
“On” represents what MPPT is operating
1
MPPT V Maximum
V
dc
0 ~ 900
Maximum voltage to run MPPT
830
MPPT V Start
V
dc
450 ~ 800
MPPT wake-up voltage
600
MPPT T Start
sec
0 ~ 600
Time delay for MPPT wake-up
300
MPPT P Stop
W
0 ~ 10000
Disconnect inverter from Grid when PV output
power is lower than the setting value of {MPPT P
Stop}.
1000
MPPT T Stop
sec
0 ~ 600
Time delay while inverter decides if PV output
power is lower than the setting value of {MPPT P
Stop}.
30
MPPT V Minimum
V
dc
200 ~ 800
Minimum voltage to run MPPT
410
Table 10: PV Array Parameters