P a r a m e t e r
P a r a m e t e r
8.3 Grid
Parameters
Parameters
Units
Ranges
Descriptions
Default
Rated Grid Voltage
V
208 ~ 400
Rated value of the grid voltage
380
Rated Grid Fre-
quency
Hz
50 ~ 60
Rated value of the grid frequency
60
Grid Over Voltage
Level 1
%
105 ~ 125
Upper limit expressed as a percentage of the rated
grid voltage for grid overvoltage level 1
110
Grid Under Voltage
Level 1
%
75 ~ 110
Lower limit expressed as a percentage of the rated
grid voltage for grid under voltage Level 1
90
Grid Over Frequency
Level 1
Hz
0.0 ~ 3.0
Upper limit for grid over frequency level 1
0.2
Grid Under Fre-
quency Level 1
Hz
0.0 ~ 3.0
Lower limit for grid under frequency level 1
2
Frequency Depend-
ant Power Reduction
Enable
N/A
On(1), Off (0)
“On” Represents what the frequency dependant
power reduction is working
0
Power Gradient
Mode
N/A
0 ~ 3
This parameter determines when “Power Gradient”
is activated.
0 : Disable
1: Activated when connected to grid after fault
(Medium Voltage Requirements)
2: Activated according to VDE-AR-N 4105 (Low
Voltage Requirements)
3: Activated whenever connected to grid (TERNA
Grid Code)
0
Power Gradient
Ramp
sec
0.0 ~ 600
Time for power gradient ramp
600
Time shift
sec
0.0 ~ 6000
Delay time for inverter start
0
Gate-way Enable
N/A
0.0 ~ 1.0
Reserved parameter
0
Grid Level 2 Protec-
tion Enable
N/A
On(1), Off (0)
“On” represents what grid level 2 protection is
working
1
Grid Over Voltage
Level 2
%
105 ~ 130
Upper limit expressed as a percentage of the rated
grid voltage for grid overvoltage level 2
120
Grid Under Voltage
Level 2
%
75 ~ 100
Lower limit expressed as a percentage of the rated
grid voltage for grid under voltage Level 2
80
Grid Under Fre-
quency Level 2
Hz
0.0 ~ 3.0
Lower limit for grid under frequency level 2
2.5
Grid Over Voltage
Level 1 Trip time
ms
1000 ~ 10000
Time for grid over voltage level 1 trip
5000
Table 12: Grid Parameters