Operating Instructions Powador XP100-HV

P a r a m e t e r

P a r a m e t e r

8.3.1

FRT Enable Off

If the function of FRT(Fault-ride through) is not active, XP100-HV parameters for abnormal grid is as follows.

Grid Under Frequency

Figure 45: Grid under frequency

1.

f < f

rated

– 2Hz, t > 10s  Grid Under Frequency Level 1 Fault

2. f < f

rated

– 2.5Hz, t > 100ms  Grid Under Frequency Level 2 Fault

Grid Over Frequency

Figure 46: Grid over frequency

1.

f < f

rated

+ 0.2Hz, t > 100ms  Over Frequency Level 1 Fault

2. It disables Grid Over Frequency Level 2 and Level 3 Faults.