1 frt enable off, Grid under frequency, Grid over frequency – KACO Powador XP100-HV User Manual
Page 56

Page 56
Operating Instructions Powador XP100-HV
P a r a m e t e r
P a r a m e t e r
8.3.1
FRT Enable Off
If the function of FRT(Fault-ride through) is not active, XP100-HV parameters for abnormal grid is as follows.
Grid Under Frequency
Figure 45: Grid under frequency
1.
f < f
rated
– 2Hz, t > 10s Grid Under Frequency Level 1 Fault
2. f < f
rated
– 2.5Hz, t > 100ms Grid Under Frequency Level 2 Fault
Grid Over Frequency
Figure 46: Grid over frequency
1.
f < f
rated
+ 0.2Hz, t > 100ms Over Frequency Level 1 Fault
2. It disables Grid Over Frequency Level 2 and Level 3 Faults.