KACO Powador XP100-HV User Manual
Page 66

Page 66
Operating Instructions Powador XP100-HV
P a r a m e t e r
Parameters
Units
Ranges
Descriptions
Default
Cabinet FAN PWM
-
0 ~ 100
Reserved parameter
100
Remote Power
Control Ramp
sec
0 ~ 600
The slope of inverter output active poser when
remote power is controlled
10
Total Yield
kWh
0 ~ 99999999
Check total yield of generation (Read only)
-
Today Yield
kWh
0 ~ 99999999
Check day yield of generation (Read only)
-
IIVCD P Gain
-
0 ~ 99999
Inverter output voltage controller’s D-axis P gain
for Initial operation voltage
0.6
IIVCD I Gain
-
0 ~ 99999
Inverter output voltage controller’s D-axis I gain for
initial operation voltage
1.5
IIVCQ P Gain
-
0 ~ 99999
Inverter output voltage controller’s Q-axis P gain
for initial operation voltage
2
IIVCQ I Gain
-
0 ~ 99999
Inverter output voltage controller’s Q-axis I gain for
Initial operation voltage
5
Anti-Islanding
Enable
-
0 ~ 99999
The use of anti-islanding controller, Yes(1) NO(0)
0
APS Line Deadband -
0 ~ 99999
The setup value for anti-islanding control
0.11
Reactive Power Limit -
0 ~ 99999
The setup value for anti-islanding control
0.06
Wind Speed
-
0 ~ 99999
Reserved parameter
-
Power Derating
Enable
-
0 ~ 1
The use of power decline controller according to
PEBB temperature, Yes(1) NO(0)
0
Power Derating
Enable Temperature
-
50 ~ 100
Temperature level which starts decreasing power
according to PEBB temperature
80
Power Derating
Disable Temperature
-
40 ~ 90
Temperature level which stops decreasing power
according to PEBB temperature
60
Power Derating
Reference Tempera-
ture
-
45 ~ 95
PEBB temperature reference value
70
Power Derating P
Gain
-
0 ~ 10
Power declining controller’s P gain according to
PEBB temperature
2
Grid IIR Filter Cutoff
Frequency
Hz
0 ~ 10
Filter cutoff frequency used for RMS value detec-
tion of grid voltage
1.5
Asynchronous Fault
Count
-
0 ~ 100
Reserved parameter
10
Asynchronous Fault
Enable
-
0 ~ 1
Reserved parameter
0
Grid Positive
Sequence
0
999.9
Positive sequence value of grid
-
Table 17: Controller Parameters