KACO Powador XP100-HV User Manual
Page 17

Operating Instructions Powador XP100-HV
Page 17
I n s t a l l a t i o n / S t a r t - u p
5.3.2
Connecting to the external transformer (AC connection)
The inverter is connected to the power grid using a 3-phase connection. The connection for the power grid is
located in the right side of the housing, at the bottom (fi gure 8).
Connection data
Max. cable diameter
300 mm²
Tightening torque for AC terminal connections
43 Nm
Cable Lug hole size
12 mm ~ 14 mm
Connect the cables
Each cable corresponds to one phase.
Guide the cables through the opening.
Be sure to connect each of the cables to the correct terminal.
Screw down the cables.
Check to make sure that all of the cables are securely attached.
Figure 8: AC connection