3 connection for the pv generator (dc connection) – KACO Powador XP100-HV User Manual
Page 18

Page 18
Operating Instructions Powador XP100-HV
I n s t a l l a t i o n / S t a r t - u p
5.3.3
Connection for the PV generator (DC connection)
The DC connection is located in the left side of the housing, at the bottom (fi gure 9).
Connection data
Tightening torque for DC terminal connections
25 Nm
DC input terminal
+4, -4
DC Fuse
+1(300A), -1(300A)
Cable Lug hole size
10 mm ~ 12 mm
DANGER
Lethal voltages in the PV system
Lethal voltages are present in the PV system.
›
Make absolutely sure that the plus and minus poles are properly insulated.
Connect the cables
Each cable corresponds to a specifi c pole.
Connect the cables to the poles.
Make sure the polarity is correct.
Screw down the cables.
Check to make sure that all of the cables and
seals are securely attached.
Figure 9: DC connection
NOTE
Use only the optional earthing kit to earth the PV generator.