1 example of power derating – KACO Powador XP100-HV User Manual
Page 71

Operating Instructions Powador XP100-HV
Page 71
P a r a m e t e r
Descriptions for sections of Example of Power Derating are:
T1: Inverter produces energy and PEBB temperature rises.
T2: When PEBB temperature is higher than 70°C, power derating is activated. And inverter controls output power
according to expression, P(%) = 100 - (T
PEBB
-60) x 2 until power derating is deactivated.
T3: Output power decrease and PEBB temperature drops. When PEBB temperature is lower than 50°C, power der-
ating is deactivated. And inverter doesn’t decrease output power.
8.7.2.1 Example of Power Derating
Figure 57: XP100-HV