Operating Instructions Powador XP100-HV
P a r a m e t e r
P a r a m e t e r
Parameters
Units
Ranges
Descriptions
Default
Grid Over Voltage
Level 2 Trip time
ms
40 ~ 2000
Time for grid over voltage level 2 trip
100
Grid Under Voltage
Level 1 Trip time
ms
1000 ~ 10000
Time for grid under voltage level 1 trip
5000
Grid Under Voltage
Level 2 Trip time
ms
40 ~ 2000
Time for grid under voltage level 2 trip
100
Grid Under Fre-
quency Level 1 Trip
time
ms
1000 ~ 20000
Time for grid under frequency level 1 trip
10000
Grid Under Fre-
quency Level 2 Trip
time
ms
40 ~ 2000
Time for grid under frequency level 2 trip
100
Grid Over Frequency
Level 1 Trip time
ms
40 ~ 2000
Time for grid over frequency level 1 trip
100
FRT Enable
N/A
On(1), Off (0)
“On” represents what FRT is working
0
Grid Over Voltage
FRT Enable
N/A
On(1), Off (0)
“On” represents what the grid overvoltage FRT is
working
0
Power Reduction
Gradient Level
%/Hz
0.0 ~ 100
Gradient level for frequency dependant power
reduction
40
Power Reduction
Deactivation
Frequency
Hz
0.0 ~ 0.3
Frequency limit for power reduction deactivation
0.05
Grid Over Frequency
Level 2
Hz
0.0 ~ 3.0
Upper limit for grid over frequency level 2
1.5
Grid Over Frequency
Level 2 Trip time
ms
40 ~ 2000
Time for grid over frequency Level 2 trip
100
Reconnection
Condition Mode
N/A
0 ~ 2
This parameter determines when “Reconnection
condition” will be checked.
0: Disable
1: Checked before connected to grid (Medium
Voltage Requirements)
2: Checked according to VDE-AR-N 4105 (Low
Voltage Requirements)
1
Reconnection
Condition Upper
Voltage
%
-1 ~ 130
This parameter represents the upper voltage in the
range of “Reconnection condition” as a percentage
of the rated value.
The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.
-1
Table 12: Grid Parameters