KACO Powador XP100-HV User Manual
Page 67

Operating Instructions Powador XP100-HV
Page 67
P a r a m e t e r
Parameters
Units
Ranges
Descriptions
Default
COSPHI Control
Mode
-
0 ~ 5
Reactive power supply method in Internal mode
and RPC mode
0: disabled
1: fi xed P
2: fi xed cos
3: fi xed Q
4: Cos(P/Pn)
5: Q(U)
2
COSPHI Internal
Power Factor
-
-0.999 ~ 1
Power factor reference in internal mode
1
COSPHI Internal
Reactive Power
%
-99.9 ~ 99.9
Reactive power reference in internal mode (Percent
for rated one)
0
COSPHI Actual
Power Factor
-
-0.999 ~ 1
The actual power factor value that is applied (Read
only)
1
COSPHI RPC Power
Factor
-
-0.999 ~ 1
Power factor reference in RPC mode
1
COSPHI RPC Reactive
Power
%
-99.9 ~ 99.9
Reactive power reference in RPC mode
(percent for rated one)
0
COSPHI Stray Ratio
-
0 ~ 2
The setup value for COSPHI control
0.985
Positive Sequence
PLL Enable
-
On(1), Off (0)
The use of grid voltage of positive sequence at PLL 1
FRT K Factor
-
0 ~ 10
The setup constant during FRT control
2
FRT IQ Ramp
ms
0 ~ 99999
The slope of active power supply during FRT
control
4000
FRT IQ Ramp Time
ms
0 ~ 99999
The time that use a slope changed by FRT IQ ramp
parameter
2000
Positive Sequence
LPF
Hz
0 ~ 100
The cutoff frequency for RMS value of positive
sequence
100
PLL Freq LPF
Hz
0 ~ 100
The cutoff frequency for frequency value detection
of PLL
100
Q(V) Control Target
Voltage
V
208 ~ 440
Value of Q(V) Control Target Voltage
380
Q(V) Control K Factor -
0 ~ 50
A setup constant for voltage control of BDEW
3.1
Q(V) Control
Deadband
%
0 ~ 100
Non-applicable voltage range during voltage
control of BDEW
1
Q(V) Control Ramp
Time
sec
0 ~ 99999
The slope of reactive current increase during
voltage control of BDEW
60
Table 17: Controller Parameters