2 frt enable on – KACO Powador XP100-HV User Manual
Page 58

Page 58
Operating Instructions Powador XP100-HV
P a r a m e t e r
8.3.2
FRT Enable On
The parameter when FRT Enable is on is as follow.
Parameters
Units
Ranges
Descriptions
Default
FRT Enable
N/A
On (1), Off (0)
“On” represents what FRT is operating
1
Grid Under Voltage
Level 2
%
75 ~ 100
Lower limit expressed as a percentage of the rated
grid voltage for grid under voltage level 2
15
Grid Under Voltage
Level 1 Trip time
ms
1000 ~ 10000
Time for grid under voltage Level 1 trip
2000
Grid Under Voltage
Level 2 Trip time
ms
40 ~ 2000
Time for grid under voltage Level 2 trip
150
MPP Range Upper
V
dc
10 ~ 300
Upper limit of maximum power point
300
MPP Range Lower
V
dc
10 ~ 300
Lower limit of maximum power point
300
Table 13: FRT Enable On
Grid Under Voltage
Figure 49: Grid under voltage
1.
U > 1.1*U
rated
, t > 2s Grid Over Voltage Level 1 Fault
2. U > 1.2*U
rated
, t > 150ms Grid Over Voltage Level 2 Fault