F a u l t s a n d W a r n i n g s
6
Faults and Warnings
When a problem occurs in the system, the Inverter will beep and inform the user on the GUI. The Inverter displays
two basic error messages. The fi rst, the fault, is a serious problem that causes the inverter to stop running. The
second, a warning, is a minor problem that does not cease the system operation. The GUI will indicate faults in red
and warnings in yellow. The user can fi nd a description of the diff erent fault and warnings in the following Tables.
6.1 Warnings
Code
Message
Description
81
SP1 (PV SP) Failure
Failure of the PV side surge protector (SP1)
82
CB10 (PV Contactor) Failure
PV side contactor (CB10) failure
83
PV Fuse Failure
PV side Fuse failure (option)
84
Ground Fault Warning
The insulation resistance of the PV falls short of the limit set in the ground
fault monitoring for Alert1 (option)
85
PV Over Voltage
PV voltage exceeds the parameter [DC over voltage Level]
100
PEBB Over Temp. Warning
The temperature of the PEBB (Power Electronics Building Block) heatsink
exceeds 75°C (167°C)
101
PEBB Fan Failure
Failure of a PEBB (Power Electronics Building Block) fan
110
SP2 (Grid SP) Failure
Failure of the grid side surge protector (SP2)
120
Test Mode
The system is working in test mode
121
Watchdog
Abnormalities detection in the DSP
125
Parameter Invalid
Parameter is invalid value
130
Cabinet Over Temp.
Warning
The temperature of the cabinet exceeds the operational parameter [Cab-
inet Temperature Maximum]
131
Cabinet Under Temp.
Warning
The temperature of the cabinet falls below the operational parameter
[Cabinet Temperature Minimum]
134
Control SMPS Failure
Failure of the control SMPS (Switching Mode Power Supply)
Table 5: Warnings