6 grid over voltage level slow – KACO Powador XP100-HV User Manual
Page 62

Page 62
Operating Instructions Powador XP100-HV
P a r a m e t e r
Power Gradient Mode
MANUAL
(Manual Operation)
NORMAL
(Normally discon-
nected from grid)
FAULT
(Disconnected from
grid due to fault)
0 (Disable)
Deactivated
Deactivated
Deactivated
1 (Activate after fault)
Deactivated
Deactivated
Activated
2 (VDE-AR-N 4105)
Deactivated
Deactivated
Activated
3 (TERNA)
Activated
Activated
Activated
Reconnection Condi-
tion Mode
MANUAL
(Manual Operation)
NORMAL
(Normally discon-
nected from grid)
FAULT
(Disconnected from
grid due to fault)
0 (Disable)
Deactivated
Deactivated
Deactivated
1 (Activate always)
Activated
Activated
Activated*
2 (VDE-AR-N 4105)
Deactivated
Activated
Activated*
* When inverter is disconnected from grid due to fault, system checks “Reconnection Condition” for the time set-
ting of {Reconnection Condition Check Time After Fault} parameter. In other cases, system checks the “Reconnec-
tion Condition” for the time setting of {Reconnection Condition Check Time Normal}.
8.3.6 Grid Over Voltage Level Slow
Figure 53: Grid Over Voltage Level Slow