P a r a m e t e r
P a r a m e t e r
Parameters
Units
Ranges
Descriptions
Default
Reconnection
Condition Lower
Voltage
%
-1 ~ 100
This parameter determines the lower voltage of
“Reconnection condition” range as a percentage of
the rated value.
The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.
95
Reconnection
Condition Upper
Frequency
Hz
-1 ~ 3
This parameter determines the upper frequency of
“Reconnection condition” range as an increment
from the rated value.
The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.
0.05
Reconnection
Condition Lower
Frequency
Hz
-1 ~ 3
This parameter determines the lower frequency of
“Reconnection condition” range as a decrement
from the rated value.
The negative value represents that the relevant
condition is not checked when an inverter decides
“Reconnection condition”.
2.5
Reconnection
Condition Check
Time Normal
sec
0 ~ 1800
This parameter is used for time check during
“Reconnection condition” for all the time except
after fault.
5
Reconnection
Condition Check
Time After Fault
sec
0 ~ 1800
This parameter is used for time check during
“Reconnection condition” for after fault only.
5
Grid Over Frequency
Level 3
Hz
0 ~ 3
Upper limit for grid over frequency level 3
2
Grid Over Frequency
Level 3 Trip Time
ms
40 ~ 2000
Time for grid over frequency Level 3 trip
100
Grid Over Voltage
Level Slow
%
105 ~ 115
This parameter represents Upper limit for the
average RMS value of grid voltage as a percentage
of the rated grid voltage.
If the average RMS value of grid voltage exceeds
this parameter setting, fault will be occurred.
(Low Voltage Requirements)
110
Grid Over Voltage
Level Slow Shift
Average Time
sec
-1 ~ 3000
This parameter determines how long the average
RMS value of grid voltage will be calculated.
(Low Voltage Requirements: 600 seconds duration)
Negative value means that the relevant function
(Grid Over Voltage level slow) is disabled.
-1
Reconnection
Condition Warning
Delay
sec
0 ~ 600
Time delay for Reconnection Condition Warning
10
Table 12: Grid Parameters