1 anti-islanding enable – KACO Powador XP100-HV User Manual
Page 69

Operating Instructions Powador XP100-HV
Page 69
Parameters
Units
Ranges
Descriptions
Default
IINV Voltage Build
Up Time
msec
0 ~ 9999
The sync of phase between inverter and grid
voltage will be checked after this time, since “Initial
voltage buildup” started (XP-TL does not apply)
100
IINV PLL Stabilization
Time
msec
0 ~ 9999
The phase between inverter and grid voltage
checked and for this time (XP-TL does not apply)
100
IINV PLL P Gain
-
0 ~ 999.99
Grid voltage PLL’s P Gain used for “Initial voltage
buildup” (XP-TL does not apply)
0.2
IINV PLL I Gain
-
0 ~ 999.99
Grid voltage PLL’s I Gain used for “Initial voltage
buildup” (XP-TL does not apply)
0.5
IINV Synchronization
Tolerance
degrees 0 ~ 20
This determines a tolerance limit when synchronize
the inverter and the grid voltage in „Initial voltage
buildup” state (XP-TL does not apply)
10
FRT Overcurrent
Protection Time
msec
0 ~ 5000
The power generation is stopped for this param-
eter value after fault clear in FRT situation
200
Table 17: Controller Parameters
8.7.1 Anti-Islanding
Enable
With activation of Anti-Islanding function, XP100-HV will detect and disconnect itself from the grid within a few
second. If the Anti-Islanding function is not activated, XP100-HV cannot disconnect itself from the grid during
grid failure, and generate power to load independently. For example, when inverter infuse 100 kW power to gird
with 100 kW load connected to PCC(Point of Common Coupling), inverter can generate output voltage indepen-
dently during grid failure, and operate itself with bearing 100 kW load.