Page 72
Operating Instructions Powador XP100-HV
P a r a m e t e r
8.7.2.2 Conceptual Relation between Output Power and Temperature
Below graph represents conceptual relation between inverter output power and heat sink temperature. The
output power is reduced in proportion to heat sink temperature but keep in mind that the power derating is
activated at 70°C and deactivated at 50°C (The activation/deactivation temperature can be tunable by parame-
ter).
Figure 58: Relation between output power and temperature
8.7.3 Cos-phi
Control
Cos-phi Control function is for controlling active and reactive power which is infused from XP inverter to the grid
with Prolog, MMI, and XCU at long distance.
Figure 59: Cos-phi Control composition