KACO Powador XP100-HV User Manual
Page 47
Operating Instructions Powador XP100-HV
Page 47
F a u l t s a n d W a r n i n g s
F a u l t s a n d W a r n i n g s
Code
Message
Warning description
Possible problem and solution(s)
34
CB20 (Grid SW) Trip
CB20(AC disconnect grid circuit
breaker) was tripped during
operation
Problem
• Short circuit in the grid
Solution(s)
• Check the wiring connections
40
Parameters Version
Error
Diff erent version between the
NVSRAM parameter table and
the program parameter table
Problem
• Diff erent version between the NVSRAM
parameter table and the program param-
eter table
Solution(s)
• Initialize the parameter menu setting in
the GUI and reset faulted parameter
• Change the PCB module
41
Flash Memory Failure C6000 DSP program fl ash
memory failure in XCU (main
control) board
Problem
• Internal C6000 error
Solution(s)
• Change the PCB module
42
FPGA Failure
FPGA failure in XCU (main con-
trol) board
Problem
• Internal FPGA error
Solution(s)
• Change the PCB module
43
DSP28x Failure
F2000 DSP failure in XCU (main
control) board
Problem
• Internal F2000 error
Solution(s)
• Change the PCB module
44
ADC Failure
ADC block failure in XCU (main
control) board
Problem
• Internal A to D converter error
Solution(s)
• Change the PCB module
50
Emergency Stop
The door is open
Problem
• Front door is open
• Broken or out of alignment door switch
Solution(s)
• Close the door
• Align or replace door switch
Table 8: Faults