2 faults – KACO Powador XP100-HV User Manual
Page 41

Operating Instructions Powador XP100-HV
Page 41
F a u l t s a n d W a r n i n g s
6.2 Faults
Code
Message
Description
01
PV Over Voltage
PV voltage exceeds the parameter [DC over voltage Level]
02
PV Over Current
PV current exceeds the parameter [DC over current Level]
03
PV Under Voltage
Voltage of the DC input is below the minimum running voltage
04
CB10 (PV Contactor) Failure
PV side contactor (CB10) failure
05
PV Polarity Failure
Polarity (+, -) of PV side is reversed
06
Ground Fault
PV side ground fault
10
Inv. Over Voltage
Over voltage on the inverter side
11
Inv. Under Voltage
Under voltage on the inverter side
12
Inv. Over Frequency
Over frequency on the inverter side
13
Inv. Under Frequency
Under frequency on the inverter side
14
Inv. Over Current
Over current on the inverter side
15
MC21 (Inv. MC) Failure
Inverter side contactor (MC21) failure
16
Inv. Phase Order
Phase order failure on the inverter side, wrong phase rotation
18
Inductor or TR Over Temp.
Inductor or Transformer temperature is above 150°C
20
PEBB 1 IGBT Fault
PEBB 1 IGBT failure
21
PEBB 2 IGBT Fault
PEBB 2 IGBT failure
22
PEBB 3 IGBT Fault
PEBB 3 IGBT failure
24
PEBB Over Temp. Analog
The temperature of the heat-sink exceeds 90°C (194°F)
25
PEBB Over Temp. Digital
The heat-sink temperature generated by the thermal trip device has
exceeded operational parameters (Thermal Switch)
30
Grid Over Voltage Level 1
Over voltage Level 1 on the grid side
31
Grid Under Voltage Level 1
Under voltage Level 1 on the grid side
32
Grid Over Frequency Level 1 Over frequency Level 1 on the grid side
33
Grid Under Frequency
Level 1
Under frequency Level 1 on the grid side
34
CB20 (Grid SW) Trip
CB20 (AC Disconnect/Grid circuit breaker) was tripped during operation
35
Grid Over Voltage Level 2
Over voltage Level 2 on the grid side
36
Grid Under Voltage Level 2
Under voltage Level 2 on the grid side
37
Grid Under Frequency
Level 2
Under frequency Level 2 on the grid side
38
Grid Over Frequency Level 2 Over frequency Level2 on the grid side
40
Parameters Version Error
Diff erent version between the NVSRAM parameter table and the pro-
gram parameter table
41
Flash Memory Failure
C6000 DSP program fl ash memory failure in XCU (main control) board