KACO Powador XP100-HV User Manual
Page 43
Operating Instructions Powador XP100-HV
Page 43
F a u l t s a n d W a r n i n g s
F a u l t s a n d W a r n i n g s
Code
Message
Warning description Possible
causes/Diagnosis
101
PEBB Fan Failure
PEBB heat-sink fan failure
Problem
• PEBB Fan Failure
Solution(s)
• Change the PEBB Fan
110
SP2 (Grid SP) Failure
Failure of the grid side surge pro-
tector (SP2)
Problem
• Lightning strike on or near the grid
system wiring
Solution(s)
• Visual inspection
• Change the SPD
120
Test Mode
The system is working in test
mode
Problem
• The system is working in test mode
Solution(s)
• Change the parameters in the GUI
130
Cabinet Over Temp.
Warning
The temperature of the cabinet
exceeds operational parameters
Problem
• Cabinet Fan Failure
Solution(s)
• Clean the air fi lters
• Change the cabinet fan
131
Cabinet Under Temp.
Warning
The temperature of the cabinet
falls below operational parame-
ters
Problem
• Ambient temperature is too low for oper-
ation
134
Control SMPS Failure
Failure of the control SMPS
Possible causes
• Failure of the control SMPS
Solution(s)
• Change the control SMPS
Table 7: Warnings