2 inverter parameters – KACO Powador XP100-HV User Manual
Page 52

Page 52
Operating Instructions Powador XP100-HV
P a r a m e t e r
P a r a m e t e r
Parameters
Units
Ranges
Descriptions
Default
DC Over Voltage
Level
V
dc
300 ~ 950
Upper limit for PV over voltage fault
950
DC Over Current
Level
%
0 ~ 150
Upper limit for PV over current fault
130
MPP Factor
N/A
0 ~ 1
Maximum power point factor
0.8
MPP Range Upper
V
dc
10 ~ 300
Upper limit of maximum power point
80
MPP Range Lower
V
dc
10 ~ 300
Lower limit of maximum power point
80
PV Operation Level
V
dc
900 ~ 950
Maximum PV operation level
930
Table 10: PV Array Parameters
8.2 Inverter
Parameters
Parameters
Units
Ranges
Descriptions
Default
Transformer & Type
N/A
0 ~ 4096
This parameter determines device specifi c informa-
tion such as a switch type on DC side and whether
the inverter has an internal transformer.
The setting value is represented by the combination
of bit fi elds as below
0
th
bit: Internal transformer
1
st
bit: Manual CB10
2
st
bit: S Phase Sensor
8
st
~ 11
st
bit: Inverter Type
1
Inverter Capacity
kW
100 ~ 500
Power Capacity of the inverter
100
Inverter Over
Current Level
%
0 ~ 200
Upper limit for inverter over current fault
130
Current Limit
%
0 ~ 150
Limit of current which produces from the inverter
100
Cabinet Temp.
Maximum
°C
30 ~ 70
Maximum cabinet temperature for warning
55
Cabinet Temp.
Minimum
°C
-25 ~ 10
Minimum cabinet temperature for warning
-15
PEBB Temperature
Unbalance Level
°C
5 ~ 30
When temperature diff erence between each PEBB
exceeds this parameter setting, warning will be
raised.
10
Table 11: Inverter Parameters