Page 29

I n s t a l l a t i o n / S t a r t - u p

5.9 MMI

submenus

5.9.1 PV

generator

String monitoring is activated

PV generator

Strings

0.0

0.0

0.0

Power (kW)

Voltage (V)

Current (A)

0.0

0.0

0.0

Return to next higher level

Buttons

Display

Meaning

Measured

values

Current measured values for

the PV generator

Strings

String monitoring is activated

Figure 18: “PV generator” screen

5.9.2 String

monitoring

Changes to the confi guration for the current sensors fi rst become eff ective after fi ve minutes.

30

25

20

Page :

15

10

5

0

0

2.4

4.8

7.2

9.6

12

Yellow bars:
Average current values,
faulty channel

Magenta dots:
Actual current
values

Green bars:
Average current values,
functioning channel

Light blue line:
Average of all channels

Strings

Return to the

previous level

Current

actual values

Only current actual values are

displayed during the fi rst fi ve
minutes after the function has
been activated.

Average

current
values of the
channels

The actual values for the last

fi ve minutes are recorded
(sampling period: every 30
seconds).

Average of

all current
values
(channels)

Average of all current values

(channels)

Figure 19: “String monitoring” screen

If the average of one channel deviates from the average of all channels by more than the specifi ed range of toler-

ance and if this persists for longer than a specifi ed delay period, this channel is assumed to be defective.

Isolation R (kΩ)

0.0

Cell Temp. (°C)

Irr. (W/m

2

)

Ambi.Temp. (°C)

Wind(m/s)

0.0