Operating Instructions Powador XP100-HV
F a u l t s a n d W a r n i n g s
F a u l t s a n d W a r n i n g s
Code
Message
Description
42
FPGA Failure
FPGA failure in XCU (main control) board
43
DSP28x Failure
F2000 DSP failure in XCU (main control) board
44
ADC Failure
ADC block failure in XCU (main control) board
45
NVSRAM Failure
NVSRAM Failure in XCU (main control) board or invalid parameter setting
46
Asynchronous
Synchronous fail of Grid and Inverter
50
Emergency Stop
A door is open
51
Cabinet Over Temp.
Temperature of cabinet is too high. Inverter has stopped operation
Table 6: Faults
6.3 Error
code
The Inverter can detect faults during operation. The inverter will display the fault in the GUI. Faults are indicated
in the GUI with an error code, and a plain text message with the error code and system plant name in the text
line will be sent to the system operator (only available if purchased and confi gured during setup). This section
describes how to recognize the types of faults and how to correct these faults.
Warnings
Code
Message
Warning description Possible
causes/Diagnosis
81
SP1 (PV SP) Failure
Failure of the PV side surge pro-
tector (SP1)
Problem
• Lightning strike on or near the PV system
wiring
Solution(s)
• Visual inspection
• Change the SPD
83
PV Fuse Failure
PV side Fuse failure (option)
Problem
• PV system wiring short
• Short circuit in the IGBT
Solution(s)
• Check the input current
• Check module wiring
• Change the FUSE
100
PEBB Over Temp.
Warning
The temperature of the heat-sink
of the PEBB exceeds 75°C (167°F)
Problem
• PEBB Fan Failure
Solution(s)
• Clean the fi lters or PEBB heat-sink fi ns
• Change the PEBB Fan
Table 7: Warnings