Operating Instructions Powador XP100-HV
F a u l t s a n d W a r n i n g s
F a u l t s a n d W a r n i n g s
Faults
Code
Message
Warning description
Possible problem and solution(s)
1
PV Over Voltage
PV voltage exceeds the param-
eter
Problem
• The voltage of the solar generator is too
high
Solution(s)
• Check the input voltage
• Check module wiring and system
2
PV Over Current
PV current exceeds the parame-
ter
Problem
• The current of the solar generator is too
high
• PV system wiring short
Solution(s)
• Check the input current
• Check module wiring and system
4
CB10 (PV CB) Trip
PV side circuit breaker (CB10)
tripped
Problem
• CB10 disconnect switch is open
• Auxiliary switch is inoperable, CB10 con-
tactor failed closed
Solution(s)
• Check the wiring connection
• Change the CB10, replace CB10 contactor
5
PV Polarity Failure
Polarity (+, -) of PV side is
reversed
Problem
• Polarity of PV side is reversed
Solution(s)
• Check the wiring connection and change
if necessary
6
Ground Fault
PV side ground fault
Problem
• DC & ground are shorted causing the
GFDI fuse to open
Solution(s)
• Check the solar generator for a ground
fault and Replace the GFDI Fuse
10
Inv. Over Voltage
Over voltage on the inverter side Problem
• The inverter voltage is too high
Solution(s)
• Check the inverter voltage
• Check the inverter parameter
Table 8: Faults