F a u l t s a n d W a r n i n g s
F a u l t s a n d W a r n i n g s
Code
Message
Warning description
Possible problem and solution(s)
11
Inv. Under Voltage
Under voltage on the inverter
side
Problem
• The inverter voltage is too low
Solution(s)
• Check the inverter voltage
• Check the inverter parameter
• Check the MC21
12
Inv. Over Frequency
Over frequency on the inverter
side
Problem
• The grid frequency is outside the permit-
ted range
Solution(s)
• Check the grid frequency
13
Inv. Under Frequency
Under frequency on the inverter
side
Problem
• The grid frequency is outside the permit-
ted range
Solution(s)
• Check the grid frequency
14
Inv. Over Current
Over current on the inverter side Problem
• Short circuit in the IGBT
• Short circuit in the Grid
Solution(s)
• Check the grid connection
• Check the inverter connection
15
MC21 Failure
Inverter AC side contactor failure Problem
• MC21 contactor is open
• Auxiliary switch is inoperable
Solution(s)
• Check the wiring connection
• Change the MC21
16
Inv. Phase Order
Phase order failure on the
inverter side
Problem
• Phase order failure on the inverter
• Wrong phase rotation
Solution(s)
• Check the wiring connection
• Reverse two phases
18
Inductor or TR Over
Temp
Inductor or transformer tempera-
ture is above 150°C
Problem
• Cabinet fan failure
Solution(s)
• Cleaning the fi lters
• Change the cabinet Fan
Table 8: Faults