beautypg.com

5 analog monitor signals – Yaskawa Varispeed 626M5 User Manual

Page 93

background image

Control Signals

4 -18

4.5 Analog Monitor Signals

The following conditions and specifications apply to analog output signals (for stand-alone drive systems M5A

only).

J

SM (Speed Meter Signal)

Connector number: 6CN

Pin number: 47

D

The motor speed can be monitored with an external speed meter connected.

D

The SM signal is a DC voltage signal that is output in proportion to the speed regardless of the direction

of rotation.

D

Use a voltmeter as the speed meter with the following specifications.

Item

Specification

Item

Voltmeter

Operation principle

Moving coil

Rating

10 V full scale

Internal resistance

10 kΩ

Grade

2.5 or over

D

The rated SM signal output (10 V) will turn ON when the motor is rotating at the speed set in C1-26

(S

100

), the rated speed set constant.

D

The SM signal level can be adjusted with C1-16 (SM

ADJ

), the control constant.

D

The C1-16 (SM

ADJ

) control constant is for speed adjustment. The actual motor speed will not be af-

fected by changing the set value of C1-16.

D

The SM signal precision is less than 3% of the rated value when the motor is in reverse operation.

J

LM (Load Rate Signal)

Connector number: 6CN

Pin number: 50

D

The load rate signal indicates the load rate based on the rated output.

D

The meter used must have the same specifications as the one for the speed meter.

D

The load rate signal level can be adjusted with C1-17 (LM

ADJ

) for control and C1-18 (L

MFS

) for full-

scale setting.

Use 6CN pin 48 and 6CN pin 49 for the 0 V on the meter.