Yaskawa Varispeed 626M5 User Manual
Page 48
Wiring
3.3.1 Wires and Suitable Crimp Connectors
3 -8
Notes: 1. Wire size is selected assuming external suspended wiring of single 3-core cables at
an ambient temperature of 30°C (86°
F
)
.
2. If ambient temperature exceeds 30°C (86°
F)
, the allowable current of wire may be lowered.
3. Temperature for each wire indicates the maximum allowable conductor temperature.
Table 3.2
400 V Class Converter Power Cable Specifications
Wire Sizes
Model
CIMR-
MR5
Terminal Symbols
Terminal
Screw
Tighten-
ing
Torque
(N S m)
UL-approved 75°C
(167°F) Temperature-
rated Copper Wire
[AWG (mm
2
)]
600 V Vinyl-
sheath Insulated
Wire (IV, VV)
60°C (140°F)
(mm
2
)
600 V Cross-
linked Polyethy-
lene Wire (IC)
90°C (194°F)
(mm
2
)
600 V Rubber-
insulated Cab-
tyre Cable (CT)
60°C (140°F)
(mm
2
)
P/¨, N/©
M6
2.94
(*1)
45P5
R/L1, S/L2, T/L3
M5
2.35
14 (2.1)
2
2
2
45P5
A1/r, A2/t
M5
2.35
14 (2.1)
2
2
2
M4
1.2 to 2.0
10 (5.3)
2
2
2
P/¨, N/©
M6
2.94
(*1)
47P5
R/L1, S/L2, T/L3
M5
2.35
14 (2.1)
2
2
2
47P5
A1/r, A2/t
M5
2.35
14 (2.1)
2
2
2
M4
1.2 to 2.0
10 (5.3)
2
2
2
P/¨, N/©
M6 × 2
2.94
(*1)
4011
R/L1, S/L2, T/L3
M6
3.4 to 4.9
12 (3.3)
3.5
2
3.5
4011
A1/r, A2/t
M4
1.2 to 2.0
14 (2.1)
2
2
2
M6, M6
3.4 to 4.9
10 (5.3)
3.5
2
2
P/¨, N/©
M6 × 2
2.94
(*1)
4015
R/L1, S/L2, T/L3
M6
3.4 to 4.9
10 (5.3)
3.5
2
3.5
4015
A1/r, A2/t
M4
1.2 to 2.0
14 (2.1)
2
2
2
M6, M6
3.4 to 4.9
10 (5.3)
3.5
2
3.5
P/¨, N/©
M6 × 2
2.94
(*1)
4018
R/L1, S/L2, T/L3
M6
3.4 to 4.9
8 (8.4)
5.5
3.5
5.5
4018
A1/r, A2/t
M4
1.2 to 2.0
14 (2.1)
2
2
2
M6, M6
3.4 to 4.9
10 (5.3)
5.5
3.5
3.5
P/¨, N/©
M6 × 2
2.94
(*1)
4022
R/L1, S/L2, T/L3
M6
3.4 to 4.9
8 (8.4)
8
3.5
8
4022
A1/r, A2/t
M4
1.2 to 2.0
14 (2.1)
2
2
2
M6, M6
3.4 to 4.9
8 (8.4)
5.5
3.5
5.5
P/¨, N/©
M6 × 2
2.94
(*1)
4030
R/L1, S/L2, T/L3
M6
3.4 to 4.9
6 (13.3)
14
5.5
14
4030
A1/r, A2/t
M4
1.2 to 2.0
14 (2.1)
2
2
2
M6, M6
3.4 to 4.9
8 (8.4)
8
5.5
5.5
P/¨, N/©
M6 × 2
2.94
(*1)
4037
R/L1, S/L2, T/L3
M6
3.4 to 4.9
4 (21.2)
22
8
22
4037
A1/r, A2/t
M4
1.2 to 2.0
14 (2.1)
2
2
2
M6, M6
3.4 to 4.9
6 (13.3)
8
5.5
8
P/¨, N/©
M6 × 2
2.94
(*1)
4045
R/L1, S/L2, T/L3
M6
3.4 to 4.9
4 (21.2)
22
14
22
4045
A1/r, A2/t
M4
1.2 to 2.0
14 (2.1)
2
2
2
M6, M6
3.4 to 4.9
6 (13.3)
14
8
8
4011 to
4045
A11/r1, A21/t1 (*2)
M4
1.2 to 2.0
14 (2.1)
2
2
2
* 1. Connect using exclusive-use connection bus bar.
* 2. Provided for open chassis type with a minimum capacity of 11 kW. Not provided for external heatsink cooling type.
Notes: 1. Wire size is selected assuming external suspended wiring of single 3-core cables at
an ambient temperature of 30°C (86°
F
)
.
3