Page 43

background image

3.1 Connection with Peripheral Units

3 -3

The following shows standard connections of the VS-626M5 with peripheral units.

Power Supply:

200 VAC,

Single-phase

Molded-case Circuit
Breaker (2MCCB) or
Ground Fault
Interrupter

Magnetic Contactor

(2MC)

*2

AC Reactor (L)*

1

Input Noise Filter

Grounding

Motor

R/L1

S/L2

T/L3

A1/r
A2/t

Connection Bus Bar

Flat Cable

P1N1 Power Supply Cable

U/T1

V/T2

W/T3

Encoder Cable

Z1, Z2, Z3

Motor Cooling Fan

Power Supply

Power Supply:

200 VAC, 3-phase (200 V Class) or

400 VAC, 3-phase (400 V Class)

Molded-case Circuit
Breaker (1MCCB) or
Ground Fault
Interrupter

Magnetic Contactor

(1MC)

*2

Molded-case
Circuit Breaker
(3MCCB)

or

Ground Fault
Interrupter

Grounding

VS-656MR5

(Converter)

VS-626M5
(Inverter)

*1

Make sure to connect an AC reactor to each Converter. Do not connect any equipment

other than the Converter to the secondary side of the AC reactor. If not observed, Con-

verter may burn out.

*2

Connect a surge absorber to the electromagnetic contactor in parallel with the coil of the

electromagnetic contactor, or otherwise the control signal lines may malfunction.

Fig 3.1

Connection with Peripheral Units for External Heatsink Cooling Type

3