12.2 Converter Faults

12 - 3

12.2 Converter Faults

If a fault occurs during operation, protective functions are activated depending on the fault and operation is

stopped. The contents of the faults are displayed numerically on the 7-segment display.

Table 12.1

Converter Faults

Fault No.

Name

Meaning

Corrective Actions

Overcurrent

Output current exceeded overcurrent
detection level.

S

Check the wiring.

S

Check the input supply voltage.

S

Check the AC reactor.

S

Check the load shaft (Inverter, Servo)

capacity.

Main circuit fuse
blown

Main circuit fuse was blown.

Check for damaged transistor, load
short circuit, ground short, etc.

Overload

Output current exceeded overload lev-
el.

S

Reduce the load.

S

Check the load shaft (Inverter, Servo)

capacity.

Output overvoltage

Output voltage exceeded overvoltage
level.
Detection level:
200 V class: Approx. 400 V
400 V class: Approx. 800 V

S

Check the input supply voltage.

S

Check the load shaft

(Inverter, Servo) capacity.

Main circuit under-
voltage

Main circuit output voltage became
lower than undervoltage detection lev-
el.

Check the input supply voltage.

Control circuit un-
dervoltage

Control circuit power supply became
lower than undervoltage detection lev-
el.

Check the control supply voltage.

Servo unit power
supply fault

Control supply voltage supplied to Ser-
vo Unit was not normal.

Check the control supply voltage.

Power supply fre-
quency fault

Excessive power supply frequency
deviation (50 Hz or 60 Hz ±5%)

Check the input power waveform.

Initial

charging

fault

Charging of main circuit capacitor was
not completed within set time.

Replace the Unit.

Power supply open
phase

An open phase occurred at input sup-
ply.

S

Check the input supply voltage.

S

Check the wiring.

Built-in MC opera-
tion fault

Magnetic contactor did not function.

Replace the Unit.

Heatsink overheat
1

Heatsink temperature exceeded upper
limit (minor fault).

Check the ambient temperature for ef-

Heatsink overheat
2

Heatsink temperature over upper limit
continued for one minute or longer.

Check the ambient temperature for ef
fective cooling.

Heatsink thermis-

Thermistor for heatsink temperature
detection was disconnected.

Replace the unit.

Heatsink thermis
tor disconnection

The ambient temperature is low
(−20°C (−4°F) or below).

Raise the ambient temperature to above
−20°C (−4°F).

Control PCB tem-
perature fault 1

Control PCB temperature exceeded
80°C (176°F) (minor fault).

Check the ambient temperature for ef-

Control PCB tem-
perature fault 2

Control PCB temperature exceeded
85°C (185°F).

Check the ambient temperature for ef
fective cooling.