beautypg.com

Yaskawa Varispeed 626M5 User Manual

Page 196

background image

12 -12

Table 12.2

Inverter Faults (continued)

Fault No.

Name

Contents

Corrective Actions

Error Code

Control cir-
cuit fault 1
(operator
transmission
error)

Transmission between the Inverter
and the Digital Operator cannot be
established until 5 seconds after
supplying power. Built-in memory
fault, WDT activated.

S

Insert the Digital Operator con-

nector again.

---

Control cir-
cuit fault 2
(operator
transmission
error)

Transmission between the Inverter
and the Digital Operator is estab-
lished once after supplying power,
but later transmission fault contin-
ues for more than 2 seconds. WDT
time exceeded.

g

S

Check the wiring of power sup-

ply signal line of 1CN.

S

Replace the control PCB.

---

YENET1200
communica-
tion signal
delay

After turning control power ON,
NC machine and YENET1200 com-
munication is not established.

S

Check the wiring of YE-

NET1200 communication line.

S

Check NC machine power sup-

ply.

---

12

Troubleshooting

This manual is related to the following products: