Control Signals

4.1.4 Details on Sequence Input Signals

4 -6

J

SV (Servo Mode Signal)

SV Function Selection:

6CN-12 will be the SV signal if bit 03 of the C1-36 selection signals (SEL1)

is turned ON.

Bit

3

C1−36

The servo mode for a solid tap or similar device will be switched to when 6CN-12 turns ON.

D

In the servo mode, the speed loop gain and other control constants for servo mode will be used.

D

The following control constants will be enabled in servo mode.

Speed control proportional gain (C1-05 and C1-07)

Speed control integral time constant (C1-06 and C1-08)

Servo mode magnetic flux level (C1-31 and C1-33)

Servo mode base speed ratio (C1-32 and C1-34)

J

PPI (P/PI Control Selection Signal)

PPI Function Selection:

6CN-15 will be the PPI signal if bit 04 of the C1-36 selection signals (SEL1)

is turned OFF.

Bit

4

C1−36

P control functions when 6CN-15 turns ON.
PI control functions when 6CN-15 turns OFF.

D

The PPI signal is used to select the P or PI control of the speed controller.

D

When the PPI signal is turned ON, the speed controller will be in P control regardless of the operating

status of the system.

D

Turn pin 15 OFF when P control is not to be performed.

J

LM10 (Load Factor Meter ×10 Selection Signal)

LM10 Function Selection: 6CN-15 will be the LM10 signal if bit 04 of the C1-36 selection signals

(SEL1) is turned ON.

Bit

4

C1−36

The LM10 signal functions when 6CN-15 turns ON.
(Not used for NC system (M5N). )

D

The LM10 signal is used to improve the signal-noise ratio of the system with light loads by increasing

the sensitivity of the load factor meter by 10 times.

J

DAS (Speed Reference Digital/Analog Selection Signal)

Analog input will be selected when 6CN-5 is turned OFF.
Digital input will be selected when 6CN-5 is turned ON.
(Not used for NC system (M5N). )

D

The DAS signal is used to select an analog input (10 V/100%) or digital input for the speed reference.

D

The analog speed reference is selected when the DAS signal is turned OFF, and the digital speed refer-

ence is selected when the DAS signal is turned ON.

D

The DAS signal can be turned ON or OFF only when the system is not operating.

D

The following four types of digital speed reference can be selected.

12-bit binary (factory setting)

3-digit BCD

2-digit BCD

Internal speed setting

D

The digital speed reference is selected with bits 7 and 6 of selection signal C1-37.

Refer to 4.3 Using a 12-bit Digital Speed Reference.

J

RST (Fault Reset Signal)

The RST signal functions when 6CN-13 turns OFF.
(Not used for NC system (M5N). )

D

The RST signal is used to reset the system after the protective circuit operates for overcurrent or over-

load protection and the probable cause is eliminated.

4