Wiring

3.3.5 Wiring the Main Circuit

3 -22

D

Example 1

MCCB

Use an exclusive noise filter

specified for inverters.

Power

Supply

MCCB

M

Other Control Device

~

Noise

Filter

VS-
656MR5

VS-
626M5

Correct

Fig 3.13

Using Input Noise Filter

D

Example 2

~

MCCB

MCCB

M

VS-
656MR5

VS-
626M5

~

MCCB

MCCB

M

VS-
656MR5

VS-
626M5

Power

Supply

Other Control Device

General

Noise

Filter

Power

Supply

Other Control Device

General

Noise

Filter

Do not use general-purpose filters

because they are not effective.

Incorrect

Incorrect

Fig 3.14

Examples of Incorrect Noise Filter Installation

J

Wiring Precautions for Converter Control Power Supply Input

Make sure to connect MCCB with the converter control power supply input terminals A1/r and A2/t to

protect wiring.

J

Wiring Precautions for Main Circuit between Converter and Inverter

Connecting the Main Circuit DC Power Supply

Connect converter main circuit DC output terminals P/¨ and N/© to inverter main circuit power supply

input terminals P/¨ and N/© using exclusive-use connection bus bar. Secure bus bar using all the power

terminal screws and tighten to torque value of 4 to 5 N·m.

Connecting the Converter Control Power Supply Output

Connect converter control power supply output terminals P1 and N1 to inverter left-side control power

supply input terminals P1 and N1 using exclusive-use power cable.

J

Wiring Precautions for Inverter Main Circuit Output

Connecting the Inverter and Motor

Connect output terminals U/T1, V/T2 and W/T3 to motor lead wires U, V and W. Connection method is

indicated on the back of the terminal cover. Verify that the motor rotates in the forward direction (CCW:

counterclockwise when viewed from the motor load side) with the forward run command.

Strict Prohibition of Connecting Input Power Supply to Output Terminals

Do not connect power to the U/T1, V/T2, or W/T3 output terminals, or otherwise the internal inverter cir-

cuits will be damaged.

Strict Prohibition of Shorting or Grounding Output Terminals

Do not touch output terminals directly with your fingers or connect output lines to the Inverter’s case. Elec-

trical shock or a ground short may occur, creating an extremely dangerous situation. Never short the output

lines.

Strict Prohibition of Connection of Phase Advancing Capacitor or Noise Filter

Never connect a phase advancing capacitor or LC/RC noise filter to the output circuit, or otherwise the

Inverter may be destroyed or internal components damaged.

3