background image

4.1 Sequence Input Signals

4 -5

J

TLH/TLL (Torque Control Signal H/L)

The TLH signal functions when 6CN-10 turns ON.
The TLL signal functions when 6CN-11 turns ON.

D

The TLH and TLL signals are used to temporarily control the torque of the motor in operation.

D

When the TLH or TLL signal is turned ON, the torque will be controlled and the TLE torque control

signal will be output.

D

The torque control level with the TLH signal input will be set between 5% and 120% of the 30-minute

rating in C1-24 (TLEXT), the external control torque limit level constant.

D

The TLL operation level will be 1/2 of the TLH operation level.

D

The TLL signal will take precedence over the TLH signal if both TLH and TLL signals are turned ON

simultaneously.

Torque control level

TLH or TLL

ON

120%

0%

D

The TLL control function will be enabled while the emergency stop is operating.

D

When the TLH or TLL signal is not used, turn 6CN-10 and 6CN-11 OFF.

J

INC (Incremental Signal)

INC Function Selection: 6CN-11 will be the INC signal if bit 0 of the C1-36 selection signals (SEL1) is

turned OFF and bit 1 is turned ON.

Bit

1 0

C1−36

The INC signal functions when 6CN-11 turns ON.

D

Used for incremental operation under orientation control.

D

The INC signal will be enabled if it is input earlier than or simultaneously with the ORT signal.

D

If the INC signal is input when the system is turned ON or during absolute positioning, an INC signal

fault (AL-65 or AL-75) will result.

D

The INC signal will start incremental operation from the stop position when the ORG signal input turns

ON. If positional precision of the system is required, execute absolute positioning first.

J

SSC (Soft Start Cancel Signal)

SSC Function Selection:

6CN-12 will be the SSC signal if bit 03 of the C1-36 selection signals (SEL1)

is turned OFF.

Bit

3

C1−36

The SSC signal functions when 6CN-12 turns ON.

D

The SSC signal cancels the soft start function (C1-10) so that the speed standard will catch up with

the speed reference for inching.

D

When the SSC signal is turned ON, the motor will be accelerated or decelerated within the shortest

period in current-limited acceleration or deceleration regardless of the acceleration or deceleration

time set in the C1-10 constant.

D

Turn pin 12 OFF when SSC is not being used.