beautypg.com

Yaskawa Varispeed 626M5 User Manual

Page 250

background image

Specifications

14.3.2 Molded Case Circuit Breaker and Magnetic Contactor

14 -46

14.3.2 Molded Case Circuit Breaker and Magnetic Contactor

An example of the molded case circuit breaker and magnetic contactor wiring is shown below.

3MCCB

R1
S1
T1

200 VAC*

R

1MCCB

S

T

3-Phase

Single-phase

1MC

2MCCB

2MC

r

t

R/L1

S/L2

T/L3

A1/r

A2/t

VS-656MR5

To Motor Cooling Fan

Main Circuit Power

Supply Input

Control Power

Supply Input

200 VAC

L

*: For 400 V Class, 3-phase 400 VAC.

Select MCCB and MC from the table below according to Converter (VS-656MR5) model.

Voltage

Class

Converter

Model

Power

Capacity

MCCB Rated Current (A)

MC Rated Current (A)

Class

Model

CIMR-

MR5

:

Capacity

(kVA)

1MCCB

2MCCB

3MCCB

1MC

2MC

23P7

7

30

3

3

20

3

25P5

9

40

3

3

30

3

27P5

12

50

3

3

40

3

2011

19

75

3

3

60

3

200 V

Class

2015

24

100

3

3

75

3

Class

2018

30

125

3

3

100

3

2022

36

150

3

3

125

3

2030

48

175

3

3

150

3

2037

60

250

3

3

200

3

45P5

9

20

3

2

15

3

47P5

12

25

3

2

20

3

4011

19

40

3

2

30

3

4015

24

50

3

2

40

3

400 V

Class

4018

30

60

3

2

50

3

Class

4022

36

75

3

2

60

3

4030

48

100

3

2

80

3

4037

60

125

3

2

100

3

4045

72

150

3

2

125

3

* A: For stand-alone drive system N: for NC system