15.3.4 Intermittent Load Operating Capacity

15 -18

15.3.4 Intermittent Load Operating Capacity

If operations, such as tapping a machine-tool or driving a conveyer table, are frequently reversed, care must

be taken in selecting the capacity. When using an operation cycle that includes acceleration/deceleration

operations such as those shown in Fig. 15.19, make a selection so that the motor equivalence efficiency

torque T

R

is less than the inverter continuous rated torque. (The maximum value of T

P

will be 120% of

the Inverter 30 min. rating.)

T

R

=

(N

m)

T

P

2

(t

r

+ t

f

) + T

L

2

t

s

t

C

Motor torque

Motor speed

t

r

t

c

t

s

T

L

T

P

T

P

N

M

Time

Time

t

f

Fig 15.19 Motor Torque and Speed Timechart

The motor reverse rating is the rating over the load where the motor load changes cyclically. When the

reverse rated output is taken to be t

1

, and with no load is taken to be t

2

, a as expressed in the following

formula is called %ED (Einschalt Dauer). t

1

+ t

2

is regulated to 10 minutes.

α

=

t

1

t

1

+ t

2

× 100

(%)