Trial Operation

6.4.2 Soft Start Time Setting (T

SFS

: C1-10)

6 -10

6.4.2 Soft Start Time Setting (T

SFS

: C1-10)

The Inverter speed base is the time set to be taken from 0 min

−1

. to the rated speed (C1-26), or from the

rated speed setting to 0 rotations/min. The reference/time relationship is shown in the following diagram.

The soft start time can be set between 0.1 and 180.0 s.
The acceleration and deceleration times may be longer than the soft start time setting due to load inertia.

Speed reference

Rated speed (C1-26)

Speed base

Time (s)

(%)

100

0

T

SFS

T

SFS

Speed

reference

and

base

Fig 6.3

Soft Start Time Setting

6.4.3 Load Factor Meter Full Scale (LM

FS

: C1-18)

The load factor meter displays the output ratio (in %) over the Motor rated output while the Motor is operat-

ing. Set the full scale value (i.e., the percentage value over the Motor continuous rating) of the load factor

meter using control constant C1-18. The setting can be between 120% and 500%.

6.4.4 Zero Speed Detection Level (ZS

LVL

: C1-19)

Use this constant to set the detection level for the zero speed signal. The standard setting is 30 min

−1

. The

setting can be between 3 and 60 min

−1

. As shown in the following diagram, the operation point has an hys-

terisis of ±2 min

−1

.

Lit when Z

SPD

is ON

(U1-10 display)

ON (contact closed)

OFF (contact open)

Motor speed

−2 +2

C1−19

0

Signal

output

Fig 6.4

Zero Speed Signal Detection Level and Operation Display

6.4.5 Speed Agree Width (AGR

BD

: C1-20)

Use this constant to set the operation level of the speed agree signal (AGR) (ON when the speed agrees).

The speed agree width can be set between 10% and 50%. The standard setting is 15%.

Lit when AGR is ON

(U1-10 display)

Standard setting

Operating

area

Note: The speed deviation shows the % value when

S

100

(C1-26) is taken to be 100%.

Setting

width

Operating area

Speed

deviation

(%)

0.24

1.2

10

15

50

Speed reference (%)

100

Fig 6.5

Speed Agree Width Settings and Operation Display