1.1 Relay Circuit Instructions
1-13
1
1.1.8 FALLING PULSE Instruction (OFF-PLS)
Outline
The OFF-PLS sets the value of the bit input to ON for one scan when the immediately-pre-
ceding value of the bit output changes from ON to OFF. The designated register is used to
store the previous value of the bit output.
Format
Parameter
Program Example
When IB00001 turns OFF, MB000101 turns ON and stays ON during 1 scan. MB000100 is
used to store the previous value of IB00001.
Parameter Name
Setting
Register No.
• Any bit type register (except for # and C register)
• Any bit type register with subscript (except for # and C regis-
ters)
Symbol: OFF-PLS
Full Name: Fall Pulse
Category: RELAY
Icon:
IB00001
MB000100
MB000101
ON
OFF
ON
OFF
ON
OFF
1 scan
1 scan