Data Address
The set contents will differ according to the function code as Table 2.5.
* 1. Request for readout from/write-in to coil or relay: Set the head bit
address of the data.
* 2. Request for continuous readout from/write-in to a register: Set head
word address of the data.
* 3. Request for discontinuous readout from/write-in to a register: Set head
word address of the data.
Table 2.5 Address Setting Range
Function Code
Data Address Setting Range
00H
Unused
Ineffective
01H
Read coil status
0 to 65535 (0 to FFFFH)
∗1
02H
Read input relay status
0 to 65535 (0 to FFFFH)
∗1
03H
Read contents of holding register
0 to 32767 (0 to 7FFFH)
∗2
04H
Read contents of input register
0 to 32767 (0 to 7FFFH)
∗2
05H
Change status of single coil
0 to 65535 (0 to FFFFH)
∗1
06H
Write into a single holding register
0 to 32767 (0 to 7FFFH)
∗2
07H
Unused
Ineffective
08H
Loop-back test
Ineffective
09H
Read contents of holding register (expanded) 0 to 32767 (0 to 7FFFH)
∗2
0AH
Read contents of input register (expanded)
0 to 32767 (0 to 7FFFH)
∗2
0BH
Write into holding register (expanded)
0 to 32767 (0 to 7FFFH)
∗2
0CH
Unused
Ineffective
0DH
Discontinuous readout of holding register
(expanded)
0 to 32767 (0 to 7FFFH)
∗3
0EH
Discontinuous write into holding register
(expanded)
0 to 32767 (0 to 7FFFH)
∗3
0FH
Change status of a multiple coil
0 to 65535 (0 to FFFFH)
∗1
10H
Write into a plurality of holding register
0 to 32767 (0 to 7FFFH)
∗2