Parameter parameter details – Yaskawa MP900 Series Machine Controller New Ladder Editor User Manual
Page 196

2.1 Message Functions
2-3
2
Parameter
Parameter Details
They adhere to contents-functions and so on and are collected into parameter numerical
order.
Table 2.1 is Parameter List.
I/O
Definition
Parameter
Name
I/O
Designation
Setting
Input
Execute
B-VAL
Send message instruction
Abort
B-VAL
Send message forced interruption instruction
Dev-Typ
I-REG
Type of transmission device
CPU module
= 8
215IF
= 1
217IF
= 5
218IF
= 6
218-02
= 16
SVB-01
= 11
Pro-Typ
I-REG
Transmission protocol
MEMOBUS
= 1
non-procedural
= 2
Cir-No
I-REG
Line No.
CPU module
= 1, 2
215IF
= 1 to 8
217IF
= 1 to 24
218IF
= 1 to 8
SVB-01
= 1 to 16
Ch-No
I-REG
Transmission buffer channel No.
CPU module
= 1, 2
215IF
= 1 to 13
217IF
= 1
218IF
= 1 to 10
SVB-01
= 1 to 8
Param
Address in-
put
Head address of set data (MW, DW, #W)
Output
Busy
B-VAL
Message is being sent.
Complete
B-VAL
The sending of the message has been completed.
Error
B-VAL
Occurrence of error
Table 2.1 Parameter List
Parameter No.
IN/OUT
Contents
MEMOBUS
Non-procedural
PARAM 00
OUT
Process result
Process result
PARAM 01
OUT
Status
Status
PARAM 02
IN
Called station number
Called station number
PARAM 03
SYS
System reserved
System reserved
PARAM 04
IN
Function code
PARAM 05
IN
Data address
Data address
PARAM 06
IN
Data size
Data size
PARAM 07
IN
Called CPU number
Called CPU number
PARAM 08
IN
Coil offset
PARAM 09
IN
Input relay offset
PARAM 10
IN
Input register offset
PARAM 11
IN
Holding register offset
Register offset
PARAM 12
SYS
For system use
For system use