Format parameter – Yaskawa MP900 Series Machine Controller New Ladder Editor User Manual
Page 143

1.7 DDC Instructions
1-133
1
Block Diagram
• When the change in deviation output (X-X’) and the previous deviation input (X’)
are the same in sign (diverging) in the differential (D) operation
The divergence differential time (Td1) is used as the differential time.
• When the change in deviation output (X-X’) and the previous deviation input (X’)
are opposite in sign (converging) in the differential (D) operation
The convergence differential time (Td2) is used as the differential time.
Format
Parameter
Parameter Name
Setting
Input
• Any integer type and real number type register
• Any integer type and real number type register with subscript
• Subscript register
• Constant
Parameter
• Register address (except for # and C registers)
• Register address with subscript (except for # and C registers)
Output
• Any integer type and real number type register (except for #
and C registers)
• Any integer type and real number type register with subscript
(except for # and C registers)
• Subscript register
Input
X
Output
Y
LIMIT, DB
+
-
+
+
Td/Ts
Z
-1
K p
Kd
Symbol: PD
Full Name: PD Control
Category: DDC
Icon: