Process result (param00) – Yaskawa MP900 Series Machine Controller New Ladder Editor User Manual
Page 197

2 Standard System Function
2.1.1 Send Message Function (MSG-SND)
2-4
Process Result (PARAM00)
The process result is output to the upper byte. The lower byte is for system analysis.
• 00xx: In process (BUSY)
• 10xx: End of process (COMPLETE)
• 8xxx: Occurrence of error (ERROR)
Error Classification
• 81xx: Function code error
The sending of an unused function code was attempted. Or, an unused function code
was received.
• 82xx: Address setting error
The data address, coil offset, input relay offset, input register offset, or holding regis-
ter offset setting is out of range.
• 83xx: Data size error
The size of the sent or received data is out of range.
• 84xx: Line No. setting error
The line No. setting is out of range.
• 85xx: Channel No. Setting error
The channel No. setting error.
• 86xx: Station address error
The station No. setting is out of range.
• 88xx: Transmission unit error
An error response was returned from the transmission unit.
• 89xx: Device selection error
A non-applicable device is selected.
PARAM 13
SYS
System reserved
System reserved
PARAM 14
SYS
System reserved
System reserved
PARAM 15
SYS
System reserved
System reserved
PARAM 16
SYS
System reserved
System reserved
Table 2.1 Parameter List (cont’d)
Parameter No.
IN/OUT
Contents
MEMOBUS
Non-procedural