2.1.2 Receive Message Function (MSG-RCV)
2-16
Status (PARAM01)
Output the status of the transmission unit. See "Status (PARAM01)" (on page 2-5) for
details.
Called Station Number (PARAM02)
The station number of sending side is output.
Function Code (PARAM04)
Output the MEMOBUS function code received. Refer to Table 2.8.
Note: 1.
−: cannot be output, OK: can be output
2. The MB, MW, IB, and IW registers can be used respectively as the
coil, holding register, input relay, and input registers during slave
operation.
Table 2.8 Function Codes
Function Code
Setting
00H
Unused
−
01H
Read coil status
OK
02H
Read input relay status
OK
03H
Read contents of holding register
OK
04H
Read contents of input register
OK
05H
Change status of single coil
OK
06H
Write into a single holding register
OK
07H
Unused
−
08H
Loop-back test
OK
09H
Read contents of holding register (expanded)
OK
0AH
Read contents of input register (expanded)
OK
0BH
Write into holding register (expanded)
OK
0CH
Unused
−
0DH
Discontinuous readout of holding register (expanded)
OK
0EH
Discontinuous write into holding register (expanded)
OK
0FH
Change status of a multiple coil
OK
10H
Write into a plurality of holding register
OK
11H to 20H
Unused
−
21H to 3FH
System reserved
−
40H to 4FH
System reserved
−
50H to
Unused
−