Parameter – Yaskawa MP900 Series Machine Controller New Ladder Editor User Manual
Page 217

2 Standard System Function
2.2.2 Data Trace Read Function (DTRC-RD)
2-24
Parameter
I/O
Definition
Parameter
Name
I/O
Designation
Setting
Input
Execute
B-VAL
Designation of the execution of data trace read
Group-No
I-REG
Designation of the data trace group No. (1 to 4)
Rec-No
I-REG
Designation of the head record No. for readout (0 to
maximum number of records-1)
Rec-Size
I-REG
Designation of the number of records requested for
readout (1 to maximum number of records)
Select
I-REG
Item to be read out (0001H to FFFFH)
Bits 0 to F correspond to data designations 1 to 16 of
the trace definition.
Dat-Adr
Address in-
put
Designation of the No. of the head register for readout
(address of MW or DW)
Output
Complete
B-VAL
Completion of trace read
Error
B-VAL
Occurrence of error
Status
I-REG
Data trace read execution status
Rec-Size
I-REG
Number of records read
Rec-Len
I-REG
Length (in words) of 1 record that is read
Table 2.10 Configuration of the Data Trace Read Execution Status (STATUS)
Name
Bit No.
Note
System reserved
bit0 to bit7
No trace definition
bit8
The function is not executed.
Group No. error
bit9
The function is not executed.
Designated record No.
error
bit10
Error in the designated
number of records read
bit11
The function is not executed.
Data storage error
bit12
The function is not executed.
System reserved
bit13
System reserved
bit14
Address input error
bit15
The function is not executed.