5 pd control instruction (pd), Outline – Yaskawa MP900 Series Machine Controller New Ladder Editor User Manual
Page 141

1.7 DDC Instructions
1-131
1
1.7.5 PD CONTROL Instruction (PD)
Outline
The PD instruction executes a PD control operation according to the contents of a previously 
set parameter table. The input (Input) to the PD operation must be integer or real number 
data. 
Double-length integer data cannot be used. The configurations of the parameter tables for 
integer and real number data are different. Operations are performed by processing each 
parameter as an integer consisting of the lower-place 16 bits.
* Relay I/O Bit Assignment
Table 1.14 Integer Type PD Instruction Parameters
ADR
Type
Symbol
Name
Specifications
I/O
0
W
RLY
Relay I/O
Relay input, relay output
∗
IN/OUT
1
W
Kp
P gain
Gain of the P offset (a gain of 1 is set to 100)
IN
2
W
Kd
D gain
Gain of the differential circuit input (a gain of 1 is set 
to 100)
IN
3
W
Td1
Divergence differential 
time
The differential time (ms) used in the case of diverg-
ing input.
IN
4
W
Td2
Convergence differential 
time
The differential time (ms) used in the case of con-
verging input.
IN
5
W
UL
Upper PD limit
Upper limit for the P + D offset
IN
6
W
LL
Lower PD limit
Lower limit for the P + D offset
IN
7
W
DB
PD output dead band
Width of the dead band for the P + D offset
IN
8
W
Y
PD output
PD offset output (also output to the A register)
OUT
9
W
X
Input value storage
Storage of the present deviation input value
OUT
BIT
Symbol
Name
Specifications
I/O
0 to 7
−
(Reserved)
Reserved relay for input
IN
8 to F
−
(Reserved)
Reserved relay for output
OUT
