Causes of minor error messages, Operating parameter erased, Limit switch Page 7: Positioning error
Page 7: Positioning error

SERVICE MANUAL TNC 306/360
Page 5
HEIDENHAIN Service
2.1 Causes of Minor Error Messages
OPERATING PARAMETERS ERASED
- With new and exchange controls, the machine parameters are always erased.
- Software replaced with different version (see section. 15.1)
- Buffer batteries and accumulator defective
- RAM error on PROCESSOR board
LIMIT SWITCH
- "Manual" operating mode:
The pre-determined software limit switch or the additional limit in the auxiliary
operating modes has been reached during traverse with the direction keys.
- "Automatic" operating mode:
The calculated position of the current block is beyond the software limit switch
range or beyond the additional limit. No positioning takes place.
Machine Parameters for Software Limit Switches
X+
X-
Y+
Y-
Default setting
Selection via M2816, M2817
Selection via M2816, M2817
Z+
Z-
IV+
IV-
Default setting
Selection via M2816, M2817
Selection via M2816, M2817
POWER INTERRUPTED
- After a reset signal at the power supply (e.g. line voltage drops)
- Important machine parameters may have been altered,
e.g. MP 10, MP 210, MP 1390, MP 4010, MP 7210 etc.
- For further causes see section 15.1 and 17.4
POSITIONING ERROR
- The position monitoring system set in the machine parameters 1410 or 1710 has
responded. (Check the approach behaviour of the axis and readjust, if necessary.)
EMERGENCY STOP
-The EMERGENCY STOP loop has been interrupted (see section 17.4).
-The PLC editor program has been translated