SERVICE MANUAL TNC 306/360
Page 5

HEIDENHAIN Service

2.1 Causes of Minor Error Messages

OPERATING PARAMETERS ERASED

- With new and exchange controls, the machine parameters are always erased.
- Software replaced with different version (see section. 15.1)
- Buffer batteries and accumulator defective
- RAM error on PROCESSOR board

LIMIT SWITCH

- "Manual" operating mode:

The pre-determined software limit switch or the additional limit in the auxiliary
operating modes has been reached during traverse with the direction keys.

- "Automatic" operating mode:

The calculated position of the current block is beyond the software limit switch
range
or beyond the additional limit. No positioning takes place.

Machine Parameters for Software Limit Switches

X+

X-

Y+

Y-

Default setting
Selection via M2816, M2817
Selection via M2816, M2817

910.0
911.0
912.0

920.0
921.0
922.0

910.1
911.1
912.1

920.1
921.1
922.1

Z+

Z-

IV+

IV-

Default setting
Selection via M2816, M2817
Selection via M2816, M2817

910.2
911.2
912.2

920.2
921.2
922.2

910.3
911.3
912.3

920.3
921.3
922.3

POWER INTERRUPTED

- After a reset signal at the power supply (e.g. line voltage drops)
- Important machine parameters may have been altered,

e.g. MP 10, MP 210, MP 1390, MP 4010, MP 7210 etc.

- For further causes see section 15.1 and 17.4

POSITIONING ERROR

- The position monitoring system set in the machine parameters 1410 or 1710 has

responded. (Check the approach behaviour of the axis and readjust, if necessary.)

EMERGENCY STOP

-The EMERGENCY STOP loop has been interrupted (see section 17.4).
-The PLC editor program has been translated