HEIDENHAIN TNC 306 Service Manual User Manual
Page 13

SERVICE MANUAL TNC 306/360
Page 9
HEIDENHAIN Service
Screen Display
(blinking error message)
Error Cause
GROSS POSITIONING ERROR
GROSS POSITIOINING ERROR
GROSS POSITIONING ERROR
GROSS POSITIONING ERROR
GROSS POSITIONING ERROR
GROSS POSITIONING ERROR
Position Monitoring (Servo Lag)
- Operation with feed pre-control:
position monitoring range exceeded (range defined
in machine parameter 1420)
- Operation with servo lag:
servo lag monitoring range exceeded (defined in
machine parameter 1720)
Monitoring of the Analog Voltage Limit
- The nominal voltage calculated by the control has
reached its limit of
±
10 V (only with feed precontrol).
Movement Monitoring
- The voltage difference calculated by the control has
reached the limit programmed in the machine para-
meter 1140.
Standstill Monitoring
- The deviation from the nominal position of an axis in
standstill has exceeded the value programmed in
machine parameter 1110.
- The nominal position was moved beyond during
positioning (overshooting).
Monitoring of Offset Voltage
- The offset voltage of 100 mV has been reached during
an automatic offset adjustment with machine parameter
1220. (see section 16.5)
Central Drive Monitoring
- An error in the configuration of the central drive has been
detected (e.g. two analog outputs are active
simultaneously).
Possible location of the error, when the error message
"GROSS POSITIONING ERROR
When this error message is generated, the error may be located in any element of the
closed loop.
e.g. - Control error (e.g. CLP board)
- Excessive offset voltage at the servo amplifier
- Monitoring function of the servo amplifier has responded
(e.g. power monitoring)
- Servo amplifier defective
- Motor, tachometer, encoder or cables defective
- Mechanical defect (bearings, spindle, guides)
- Excessive mechanical forces on a drive