beautypg.com

Synchronous operation of multiple devices – Measurement Computing Data Acquisition Systems rev.10.4 User Manual

Page 39

background image

Programmer’s Manual

908494

Using Multiple Devices 3-3

Synchronous Operation of Multiple Devices

The following sections describe methods for synchronizing input data with multiple DaqX compatible

devices. Three synchronization methods will be discussed:

o

Internal Clock Method

o

Master Clock Method

o

External Clock Method

The synchronization method available depends upon the device, i.e., its ability to be externally triggered

or externally clocked. The following table shows the capabilities of each device as well as the physical

location of the external trigger and pacer input/output clocks.

Device

External TTL Trigger

External Acquisition

Pacer Clock

Min. External

Clock Interval

Acquisition Pacer

Clock Output

WaveBook/512

Yes (pin 13 on DB25F)

No

NA

No

WaveBook/516

Yes (pin 13 on DB25F)

Yes (pin 20 on DB25F)

1us (1MHz)

No

DaqBooks

Yes (P1; pin 25)

No

NA

No

Daq PC-Card

Yes (P1; pin 25)

No

NA

No

DaqBoard(ISA)

Yes (P1; pin 25)

No

NA

No

TempBook

Yes

No NA No

DaqBoard/500 Series

Yes (pin 6 on SCSI ;
TTLTRG on TB-100)

Yes (pin 2 on SCSI ;
XAPCR on TB-100)

5us (200kHz)

Yes (pin 2 on SCSI ;
XAPCR on TB-100)

DaqBoard/1000 Series

Yes (pin 6 on SCSI ;
TTLTRG on TB-100)

Yes (pin 2 on SCSI ;
XAPCR on TB-100)

5us (200kHz)

Yes (pin 2 on SCSI ;
XAPCR on TB-100)

DaqBoard/2000 Series

1

Yes (P1; pin 25)

Note 2

Yes (P1; pin 20)

Note 2

5us (200kHz)

Yes (P1;pin 20)

Note 2

DaqBoard/2000c Series

1

Yes (P1; pin 25)

Note 2

Yes (P1; pin 20)

Note 2

5us (200kHz)

Yes (P1; pin 20)

Note 2

DaqBook/2000 Series

Yes (P1; pin 25)

Note 3

Yes (P1; pin 20)

Note 3

5us (200kHz)

Yes (P1; pin 20)

Note 3

DaqScan/2000 Series

Yes (P1; pin 25)

Yes (P1; pin 20)

5us (200kHz)

Yes (P1; pin 20)

DaqLab/2000 Series

Yes (P1; pin 25)

Yes (P1; pin 20)

5us (200kHz)

Yes (P1; pin 20)

DaqBoard/3000 Series

Yes (pin 6 on SCSI;
TTLTRG on TB-100)

Yes (pin 2 on SCSI ;
XAPCR on TB-100)

1us (1MHz)

Yes (pin 2 on SCSI ;
XAPCR on TB-100)

Synchronization Methods Available

Device

Internal Clock

Method

Master Clock

Method

External Clock

Method

WaveBook/512 Yes

No

No

WaveBook/516 Yes

Slave

only

Yes

DaqBooks Yes

No

No

Daq PC Card

Yes

No

No

DaqBoard(ISA) Yes

No

No

TempBook Yes

No

No

DaqBoard/500 Series

Yes

No

Yes

DaqBoard/1000 Series

Yes

Master or Slave

Yes

DaqBoard/2000 Series

Note 1

Yes

Master or Slave

Yes

cPCI DaqBoard/2000c Series

Note 1

Yes

Master or Slave

Yes

DaqBook/2000 Series

Yes

Master or Slave

Yes

DaqScan/2000 Series

Yes

Master or Slave

Yes

DaqLab/2000 Series

Yes

Master or Slave

Yes

DaqBoard/3000 Series

Yes

Master or Slave

Yes

Notes:

1 Excludes DaqBoard/2003 and cPCI DaqBoard/2003c.

2 The P1 connector for DaqBoard/2000 Series and DaqBoard/2000c Series boards is obtained by connecting a

DBK200 Series option to the board’s P4 connector.

3 DaqBook/2020 has a BNC connector for External TTL Trigger and a BNC connector for the external pacer clock.

These BNC connectors are in addition to P1 connector pins 25 and 20.