Measurement Computing Data Acquisition Systems rev.10.4 User Manual
Page 307

The range of trigger values defined by the variance and level parameters depends also upon the
trigSensitivity
setting and the type of input channel that is configured as the trigger channel. The following
table describes how the the trigSource and trigSensitivity parameters influence the trigger values
established by the level and variance parameters.
DatsHardwareAnalog
can only be used when the trigger channel is first channel in the scan
group configuration (see daqAdcSetScan)
Interaction of Trigger Variance with Trigger Level and Trigger Sensitivities
Trigger Start/Stop
Source
Trigger
Sensitivities
Trigger Start/Stop Criteria
DetsRisingEdge
Triggers/Stops when: signal value < (level-variance)
Then, signal value > level
DetsFallingEdge
Triggers/Stops when: signal value > (level+variance)
Then, signal value < level
DetsAboveLevel
Triggers/Stops when: signal value > (level)
Analog (P1)
DatsHardwareAnalog
DetsBelowLevel
Triggers/Stops when: signal value < (level)
DetsRisingEdge
Triggers/Stops when: signal value < (level-variance)
Then, signal value > level
DetsFallingEdge
Triggers/Stops when: signal value > (level+variance)
Then, signal value < level
DetsAboveLevel
Triggers/Stops when: signal value > (level)
DetsBelowLevel
Triggers/Stops when: signal value < (level)
DetsEQLevel
Triggers/Stops when: (level-variance)< signal value
< (level+variance)
Analog (P1)
DatsSoftwareAnalog
DetsNELevel
Triggers/Stops when: signal value < (level-variance)
or
signal value > (level+variance)
DetsAboveLevel
Triggers/Stops when:
Dig channel bank > (level AND(bitwise)variance)
DetsBelowLevel
Triggers/Stops when:
Dig channel bank < (level AND(bitwise)variance)
DetsEQLevel
Triggers/Stops when:
Dig channel bank = (level AND(bitwise)variance)
DetsNELevel
Triggers/Stops when:
Dig channel bank != (level AND(bitwise)variance)
Digital (P2/P3)
DatsDigPattern
DetsRisingEdge
Triggers/Stops when:
counter channel < (level-variance) Then,
counter channel > level
DetsFallingEdge
Triggers/Stops when: counter channel > (level+variance)
Then, counter channel < level
DetsAboveLevel
Triggers/Stops when: Counter channel > (level-variance)
DetsBelowLevel
Triggers/Stops when: Counter channel < (level+variance)
DetsEQLevel
Triggers/Stops when:
(level-variance)< counter channel < (level+variance)
Counter (P3)
DatsCounter
DetsNELevel
Triggers/Stops when: Counter channel < (level-variance)
Or
counter channel > (level+variance)
Programmer’s Manual
908594
Daq API Command Reference 4.6-29