beautypg.com

Measurement Computing Data Acquisition Systems rev.10.4 User Manual

Page 307

background image

The range of trigger values defined by the variance and level parameters depends also upon the
trigSensitivity

setting and the type of input channel that is configured as the trigger channel. The following

table describes how the the trigSource and trigSensitivity parameters influence the trigger values
established by the level and variance parameters.

DatsHardwareAnalog

can only be used when the trigger channel is first channel in the scan

group configuration (see daqAdcSetScan)

Interaction of Trigger Variance with Trigger Level and Trigger Sensitivities

Trigger Start/Stop

Source

Trigger

Sensitivities

Trigger Start/Stop Criteria

DetsRisingEdge

Triggers/Stops when: signal value < (level-variance)
Then, signal value > level

DetsFallingEdge

Triggers/Stops when: signal value > (level+variance)
Then, signal value < level

DetsAboveLevel

Triggers/Stops when: signal value > (level)

Analog (P1)
DatsHardwareAnalog


DetsBelowLevel

Triggers/Stops when: signal value < (level)

DetsRisingEdge

Triggers/Stops when: signal value < (level-variance)
Then, signal value > level

DetsFallingEdge

Triggers/Stops when: signal value > (level+variance)
Then, signal value < level

DetsAboveLevel

Triggers/Stops when: signal value > (level)

DetsBelowLevel

Triggers/Stops when: signal value < (level)

DetsEQLevel

Triggers/Stops when: (level-variance)< signal value
< (level+variance)

Analog (P1)
DatsSoftwareAnalog

DetsNELevel

Triggers/Stops when: signal value < (level-variance)
or

signal value > (level+variance)

DetsAboveLevel

Triggers/Stops when:
Dig channel bank > (level AND(bitwise)variance)

DetsBelowLevel

Triggers/Stops when:
Dig channel bank < (level AND(bitwise)variance)

DetsEQLevel

Triggers/Stops when:
Dig channel bank = (level AND(bitwise)variance)

DetsNELevel

Triggers/Stops when:
Dig channel bank != (level AND(bitwise)variance)

Digital (P2/P3)
DatsDigPattern

DetsRisingEdge

Triggers/Stops when:
counter channel < (level-variance) Then,
counter channel > level

DetsFallingEdge

Triggers/Stops when: counter channel > (level+variance)
Then, counter channel < level

DetsAboveLevel

Triggers/Stops when: Counter channel > (level-variance)

DetsBelowLevel

Triggers/Stops when: Counter channel < (level+variance)

DetsEQLevel

Triggers/Stops when:
(level-variance)< counter channel < (level+variance)

Counter (P3)
DatsCounter

DetsNELevel

Triggers/Stops when: Counter channel < (level-variance)
Or

counter channel > (level+variance)

Programmer’s Manual

908594