RPC with or without Ethernet

55

A Unit Reset takes approximately 10 seconds for the unit to reset. It will not affect the state the
energized outlets are in. It will not reset the unit to “Factory Default”, but it will terminate the external
communications.

Logout

Select T), will close the session to the unit, but may not close the terminal emulator session.

Troubleshooting:

Diagnostic LED Indications

To detect hardware, cabling, or configuration problems upon initialization of power, the RPC Series go
through a diagnostic sequence. To help determine the cause of the problem, the RPC Series have a CX
LED located on the front, right side of the unit. Upon initialization of power, refer to the table below
for interpretation.


INDICATION INTERPRETATION
Not lit

Normal unconnected operation

Brief flash followed by a solid illumination

Established connection on network port or
serial port

Flashes 1 time per cycle

Hardware or NIC problem

Flashes 2 times per cycle

Configuration error

Flashes 3 times per cycle

Cable or hub connection fault

Flashes 4 times per cycle

Duplicate IP address

Remains lit without a brief flash prior to
illumination

Memory error


NOTE:
Diagnostic indications override a connection indication.