Help options, Receptacle controls – BayTech RPC Single-phase Conbined QS User Manual
Page 21
RPC with or without Ethernet
20
Type ‘help’ at the RPC prompt will display a list of commands to change the state of the outlets, unit
configuration, and internal sensor measurements.
HELP Options
Receptacle Controls
On, Off, Reboot, Lock, and Unlock are commands to control the individual outlets.
From the (RPC >) prompt, enter one of the following commands: ON n, OFF n, REBOOT n, where
“n” is the outlet number you want to command.
Example: To turn “On” Outlet 3, type ON 3 from the RPC prompt. If the confirmation option is turned
on, the RPC will display the following:
Type “Y” for yes or “N” for no. Likewise, typing ‘ON ALL’, ‘ON 0’, or ‘ON’ at the RPC > prompt
and responding “Y” for yes, turns ‘On’ all outlets. The OFF n command work similarly as the ON n
command.
The REBOOT n command will reboot or reset equipment attached to corresponding receptacle(s).
When the command to REBOOT (n) is sent from the RPC > prompt, the RPC powers ‘Off’ the
corresponding outlet(s) for approximately 10 seconds, then powers them ‘On’ in sequence.
This command only works on outlets which were ‘On’ prior to receiving the reboot command.
The LOCK n command is an admin user only command. This command allows the admin user to
lock an outlet in its current state. The user assigned to the outlet will not be able to change the outlet’s
state.
Example: To lock Outlet 1, type lock 1 at the RPC prompt.
RPC-4>help
On n
Off n
Reboot n
Status
Config
Lock n
Unlock n
Current
Voltage
Power
Clear
Temp
Logout
Logoff
Exit
Password
Whoami
Unitid
Type Help for a list of commands
Enter Request:
Turn On Outlet 3 (Y/N)?