Selecting the Environmental Sensor with a probe attached the RPC will display the following:

Select 1), the RPC displays:

Selecting probe 2 displays a recognized temperature probe:

Option 1 and 3 sets the temperature levels to the tenth of a degree. Option 2 and 4 enable the SNMP
traps to be sent if the corresponding threshold had been exceeded.

Select 2), ‘All Sensors’ option allows the administrator to set parameters for the different probe types.
This feature is useful for standardization and the probe type is not known due to its final location is not
known. The RPC displays:

None of the installed devices support this option (no temperature probes installed).

Strike ENTER to continue

Environmental Sensor Configuration Menu
Sel M/P Identifier
1 2/1 RPC3ADE
2 All Sensors
Enter Request :1

Sel Type Name Hi/En Lo/En St/En
1 Contact External Sensor1 N/A N/A Ds
2 Temperature External Sensor2 0/Ds 0/Ds N/A
Enter Request :2

RPC/RPS External Environmental Sensor Configuration Menu
Sensor Number: 2 Name: External Sensor2 Type: Temperature

1...High Threshold (tenths of meas. unit): 0
2...High Threshold Trap Enable: Disabled
3...Low Threshold (tenths of meas. unit): 0
4...Low Threshold Trap Enable: Disabled

Enter Request :1

Sel Type Name Hi/En Lo/En St/En
1 Contact External Sensor1 N/A N/A En
2 Temperature External Sensor2 999/En 320/En N/A

For configuration of all sensors of selected type in system with a
single user-supplied value.

1...Contact
2...Temperature
3...Humidity
4...Air Flow
Enter Request :1