Temperature alarm threshold, Under voltage alarm threshold, Over voltage alarm threshold – BayTech RPC Single-phase Conbined QS User Manual
Page 52: Low current alarm threshold
RPC with or without Ethernet
51
Internal Alarm Threshold
Select any alarm threshold option and the RPC will display the following:
Temperature Alarm Threshold:
Under Voltage Alarm Threshold:
Over Voltage Alarm Threshold:
Low Current Alarm Threshold
Enter the Selection number and the unit will display one of the following dependent on the alarm:
NOTE: M/P = Module number and Port number; Identifier = this unit’s model number; Tmp
Lvl = temperature level, Lo V Lvl = low voltage level, Hi V Lvl = High voltage level, low Curr
= Low Current. The unit’s firmware determines whether the degrees are Celsius or Fahrenheit.
Currently there is no option to change the degrees.
External Alarm Threshold
Selecting the Environmental Sensors with no probes attached the RPC will display the following:
Host-controlled RPC Feature Configuration
Temperature Alarm Threshold........1
Under Voltage Alarm Threshold......2
Over Voltage Alarm Threshold.......3
Low Current Alarm Threshold........4
Environmental Sensors..............5
Outlet Groups......................6
Sel M/P Identifier Tmp Lvl
1 2/1 RPC3ADE 500
Sel M/P Identifier Lo V Lvl
1 2/1 RPC3ADE 900
Sel M/P Identifier Hi V Lvl
1 2/1 RPC3ADE 1300
Sel M/P Identifier Low Curr
1 2/1 RPC3ADE 0
Enter threshold value in tenths of unit measurement (degrees,%,etc.):
Enter voltage threshold value in tenths of a volt:
Enter low current threshold value in tenths of an amp: